BD Module: LX3V-2TC2DAI-BD

The LX3V-2TC2DAI-BD is a versatile temperature and analog input/output module designed for efficient data processing. It features 2 thermal resistance inputs (thermocouple types K or J), with a wide temperature range of -100°C to 1200°C for K-type and -100°C to 600°C for J-type thermocouples.

Description

The LX3V-2TC2DAI-BD is a versatile temperature and analog input/output module designed for efficient data processing. It features 2 thermal resistance inputs (thermocouple types K or J), with a wide temperature range of -100°C to 1200°C for K-type and -100°C to 600°C for J-type thermocouples. The module provides 2 analog outputs (4~20mA) and offers high precision with 12-bit resolution, ensuring accurate readings and reliable performance. It supports both digital and analog outputs, with an overall accuracy of ±0.5%. Powered by a 24VDC or 5VDC supply, it operates seamlessly within PLC systems, making it ideal for industrial automation applications.

Key Features:

  • Dual thermocouple inputs (K/J type)
  • 4~20mA analog output
  • 12-bit resolution and ±0.5% accuracy
  • Conversion rate of 50ms
  • No insulation between PLC channels
  • Powered by PLC host (24VDC or 5VDC)

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

Technical Data

Item LX3V-2TC2DAI-BD
Power supply 24VDC±10%,50mA; 5VDC±10%, 70mA (Powered by PLC host)
Temperature input (TC)
Analog input signal Thermocouple: K or J type, 2 channels (CH1, CH2)
Range of rated temperature K: -100℃ – 1200 ℃ J: -100℃ – 600 ℃
Digital output K: -1000 – 12000 J: -1000 – 6000
12 bits total
Accuracy K: 0.4 ℃ J: 0.3 ℃
Overall accuracy ±0.5%
Conversion rate 50ms
Conversion characteristics image.png
Analog output (DAI)
Rated range 4~20mA: 0~2000
Analog output DC 4~20mA (the external load resistance is no less than 500Ω)
Digital output 12 bit binary
Resolution 8uA [4~20mA / 2000]
Precision ±0.5% of full scale
AD conversion time One PLC scanning cycle
Input characteristics

The external load is 250Ω and 0-2000 is converted to 4-20mA

image.png

Insulation No insulation in each PLC channel
Occupied points None